Combined Earth Fault and Over Current Numerical Relay Kit Manufacturer,Supplier and Exporter in India

Product Code : SCL-EELE-12996

Indian Lab Suppliers supplies the Combined Earth Fault and Over Current Numerical Relay Kit (Product ID: 12996) as part of its electronics engineering lab equipment range. It is a rack-mounted kit for testing a numerical relay that combines IDMT overcurrent and earth fault protection.

Quick Answer

Test current is set with a single-phase dimmer (230 V, 1 A) feeding a short-circuit transformer (230 V, 1 A primary; 0–2–8 V, 12 A secondary taps), which gives the high current at low voltage needed to operate the relay. An over-current and elapsed-time panel with a 20 A ammeter records the trip time up to 999 s at 1 ms resolution, and all relay connections, including 2 NO trip contacts, are brought out on the relay panel. The relay is rated 5 A with an adjustable current setting. Two experiments are listed: IDMT overcurrent protection and earth fault protection. Please confirm the relay setting ranges at quotation.

Key Specifications

ParameterDetail
Input panelSingle phase AC; MCBs 4 A and 1.6 A; bulb load
Injector1-phase dimmer 230 V / 1 A; short-circuit transformer 230 V / 1 A primary, 0–2–8 V / 12 A secondary
Timer panelAC ammeter 20 A; elapsed time up to 999 s, 1 ms resolution
RelayNumerical IDMT overcurrent with earth fault, 5 A, adjustable current setting
Relay panelAll connections brought out; 2 NO trip contacts
FrameAluminium profile rack with ABS panels and 4 mm shrouded sockets

Where This Is Used

Used in protection laboratories for overcurrent and earth fault relay tests. The injector secondary carries up to 12 A and the transformer and leads warm up, so keep test runs short and connect with the supply off. Related: Three Phase Over Current & Earth Fault Numeric Relay Testing System (Product ID: 12985) and Earth Fault Relay Testing System (Product ID: 12979). Browse the full Electronics Engineering Lab Equipment range or related Electricity and Magnetism products.

Frequently Asked Questions

How is high test current produced?
With a short-circuit transformer giving up to 12 A at 2 or 8 V.

What is the relay current rating?
5 A.

What is the timer resolution?
1 ms.