Distance Protection Relay Trainer Manufacturer,Supplier and Exporter in India

Distance Protection Relay Trainer

Product Code : SCL-EELE-12856

Indian Lab Suppliers supplies the Distance Protection Relay Trainer (Product ID: 12856) as part of its electronics engineering lab equipment range. It is a protection trainer for a numerical distance relay on a simulated transmission line, including auto-reclose.

Quick Answer

A line panel models a short, medium (125 km) or long (250 km) line from six each of 10 Ω / 600 W resistors, 0.15 H / 5 A inductors and 2.2 µF / 630 V capacitors, with two cooling fans. Six 5/5 A CTs and a 415/110 V, 50 VA star/star voltage transformer feed a numerical distance relay (1 A / 5 A) with trip and auto-reclose contacts, RS-232 PC link, a USB converter and setting software. Students apply LG, LL, LLG, LLL and LLLG faults, check that the relay trips on the faulted zone and see it reclose after a transient fault, with two three-phase meters recording the system. The trainer is supplied from 415 V three-phase through a DOL starter, so faults should be applied only under qualified supervision.

Key Specifications

ParameterDetail
RelayNumerical distance relay, 1 A/5 A; 2 NO + 1 NC trip, 1 NO auto-reclose; aux 230 V AC; RS-232 with USB converter and setting software
Line panelR 10 Ω/600 W, L 0.15 H/5 A, C 2.2 µF/630 V, 6 each; short, 125 km and 250 km models; fan cooled
Instrument transformers6 × 5/5 A CTs; 415/110 V, 50 VA star/star VT
Metering2 three-phase multifunction meters (RS-485 Modbus optional)
Input panels3-phase DOL starter with overload relay and reclose/trip contacts; 1-phase input; FWD-OFF-REV switch 6 A/440 V
Load3 × 600 W resistors, 100-225 Ω taps
Dimensions1165 (L) × 300 (W) × 990 (H) mm

Where This Is Used

Used in power system protection labs alongside the Power Transmission Line Trainer (Product ID: 12853); feeder and transformer protection are covered by the Feeder Management Relay Trainer (Numerical) (Product ID: 12858) and the Percentage Biased Differential Relay Trainer (Electromech / Numeric) (Product ID: 12855). Browse the full Electronics Engineering Lab Equipment range or related Electricity and Magnetism products.

Frequently Asked Questions

Which faults can be applied?
LG, LL, LLG, LLL and LLLG faults on the simulated line.

Is auto-reclose shown?
Yes, for transient faults.

How is the relay set?
Through its PC link and setting software.

Related Categories

Electronics Engineering Lab Equipment · Electricity and Magnetism · Engineering Lab Equipment

Request a Quote

For pricing, bulk quantities or tender documentation on the Distance Protection Relay Trainer, reach our team via Contact Us or submit your requirement through our Tenders page.

   

Office Address

Works: #975 Malleshwaram,
Bengaluru, Karnataka 560003

[email protected]

Follow Us