A line panel models a short, medium (125 km) or long (250 km) line from six each of 10 Ω / 600 W resistors, 0.15 H / 5 A inductors and 2.2 µF / 630 V capacitors, with two cooling fans. Six 5/5 A CTs and a 415/110 V, 50 VA star/star voltage transformer feed a numerical distance relay (1 A / 5 A) with trip and auto-reclose contacts, RS-232 PC link, a USB converter and setting software. Students apply LG, LL, LLG, LLL and LLLG faults, check that the relay trips on the faulted zone and see it reclose after a transient fault, with two three-phase meters recording the system. The trainer is supplied from 415 V three-phase through a DOL starter, so faults should be applied only under qualified supervision.
Key Specifications
| Parameter | Detail |
|---|---|
| Relay | Numerical distance relay, 1 A/5 A; 2 NO + 1 NC trip, 1 NO auto-reclose; aux 230 V AC; RS-232 with USB converter and setting software |
| Line panel | R 10 Ω/600 W, L 0.15 H/5 A, C 2.2 µF/630 V, 6 each; short, 125 km and 250 km models; fan cooled |
| Instrument transformers | 6 × 5/5 A CTs; 415/110 V, 50 VA star/star VT |
| Metering | 2 three-phase multifunction meters (RS-485 Modbus optional) |
| Input panels | 3-phase DOL starter with overload relay and reclose/trip contacts; 1-phase input; FWD-OFF-REV switch 6 A/440 V |
| Load | 3 × 600 W resistors, 100-225 Ω taps |
| Dimensions | 1165 (L) × 300 (W) × 990 (H) mm |
Where This Is Used
Used in power system protection labs alongside the Power Transmission Line Trainer (Product ID: 12853); feeder and transformer protection are covered by the Feeder Management Relay Trainer (Numerical) (Product ID: 12858) and the Percentage Biased Differential Relay Trainer (Electromech / Numeric) (Product ID: 12855). Browse the full Electronics Engineering Lab Equipment range or related Electricity and Magnetism products.
Frequently Asked Questions
Which faults can be applied?
LG, LL, LLG, LLL and LLLG faults on the simulated line.
Is auto-reclose shown?
Yes, for transient faults.
How is the relay set?
Through its PC link and setting software.